Distributor Selection

Select the distributor you would like to use for your shopping cart.

Distributor

Easily check product availability and place your order with our recommended distributor.

Residual Current Circuit Breaker with Overcurrent Protection Zoomed Image
ABB

Residual Current Circuit Breaker with Overcurrent Protection

1P+N electronic RCBO in one-module width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct contacts (with sensitivity = 30 mA). Presence of neutral (blue or black) and functional earth (white) flying leads. The neutral is unswitched

Product details

SKU Code: 2CSR255151R1065

EAN Code: 8012542399629

Minimum order: 1

Available for Back Order (3 sellers)

Availability

Control Components Anglia

Back Order Call for availability on 0345 030 60 80

£71.77

Farnell

Back Order Manufacturer lead time of 7 weeks.

£60.21

RS Components

Back Order

£62.11

Distributor Availability Price  
Control Components Anglia Back Order Call for availability on 0345 030 60 80 £71.77 Ex. VAT
Farnell Back Order Manufacturer lead time of 7 weeks. £60.21 Ex. VAT
RS Components Back Order £62.11 Ex. VAT

Price Range:

£60.21 > £71.77 ex. vat

17 loyalty points

Technical Data

Main Features

EFI00218

2.712593

EFI07515

-13|131

EFI07337

0.0015|0.0387

EFI07343

0.0015|0.0248

Voltage type

AC

Built-in depth

68.9 mm

Rated current

6 A

Rated voltage

240 V

Release characteristic

B

Rated insulation voltage Ui

500 V

Rated fault current

0.03 A

Leakage current type

A

Surge current capacity

0.25 kA

Current limiting class

3

Over voltage category

3

Pollution degree

2

Width in number of modular spacings

1

Frequency

50/60 Hz

Degree of protection (IP)

IP20

Number of protected poles

1

Concurrently switching neutral conductor

no

Rated short-circuit breaking capacity according to IEC 60947-2

-

Connectable conductor cross section solid-core

1 - 25 mm²

Connectable conductor cross section multi-wired

1 - 16 mm²

With interlocking device

yes

Ambient temperature during operating

-25 - 55 °C

Flush-mounted installation

no

Number of poles (total)

2

Anti-nuisance tripping version

no

Rated impulse withstand voltage Uimp

4 kV

Rated short-circuit breaking capacity Icn according to EN 61009-1

6 kA

Disconnection characteristic

Undelayed

Rated short-circuit breaking capacity according to EN 61009

6 kA

Downloads