Distributor Selection

Select the distributor you would like to use for your shopping cart.

Distributor

Easily check product availability and place your order with our recommended distributor.

High Performance MCB Zoomed Image
ABB

High Performance MCB

The S802S-C10 is a 2-pole High Performance Circuit breaker with C-characteristic, with cage terminal and a rated current of 10 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-C10 complies with IEC/EN 60898-1 and IEC/EN 60947-2 and allows the use for residential, commercial and industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-C10 more comfortable. Due to the fast arc extinction of S802S-C10 your application will be secured.

Product details

SKU Code: 2CCS862001R0104

EAN Code: 7612271200602

Minimum order: 1

Available for Back Order (3 sellers)

Availability

Control Components Anglia

Back Order Call for availability on 0345 030 60 80

£158.88

Farnell

Back Order Manufacturer lead time of 4 weeks.

£132.58

RS Components

Back Order

£132.58

Distributor Availability Price  
Control Components Anglia Back Order Call for availability on 0345 030 60 80 £158.88 Ex. VAT
Farnell Back Order Manufacturer lead time of 4 weeks. £132.58 Ex. VAT
RS Components Back Order £132.58 Ex. VAT

Price Range:

£132.58 > £158.88 ex. vat

76 loyalty points

Technical Data

Main Features

EFI00218

3.248025

EFI07515

-13|140

EFI07337

0|0.1085

EFI07343

0|0.0775

Voltage type

Other

Built-in depth

82.5 mm

Rated current

10 A

Rated voltage

400 V

Frequency

50 - 60 Hz

Release characteristic

C

Rated insulation voltage Ui

690 V

Current limiting class

3

Over voltage category

4

Pollution degree

3

Width in number of modular spacings

3

Explosion-proof

no

Degree of protection (IP)

IP20

Number of protected poles

2

Concurrently switching neutral conductor

no

Connectable conductor cross section solid-core

Connectable conductor cross section multi-wired

Ambient temperature during operating

-25 - 60 °C

Flush-mounted installation

no

Additional equipment possible

yes

Number of poles (total)

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

25 kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

-

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

30 kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

50 kA

Rated impulse withstand voltage Uimp

8 kV

Downloads